Firmware 1.7.0 and 1.11 configurations comparison
Description
This document summarizes configuration differences between WCC Lite firmware versions 1.7.0 and 1.11. Each protocol section contains two separate tables: one for Device Sheet and one for Signal Sheet, following the original documentation structure.
(-) indicates that parameter does not exist
(+) indicates that parameter exists
MODBUS Master
Signal sheet:
Parameter |
1.7.0 |
1.11 |
Description |
Periodic_update_ms |
- |
+ |
Signal value will be published periodically according to the value set.
|
MODBUS Slave
Device sheet:
Parameter |
1.7.0 |
1.11 |
Description |
Respond_delay |
- |
+ |
Time in milliseconds to wait before sending responses. Disabled if the value is set to 0 |
Signal sheet:
Parameter |
1.7.0 |
1.11 |
Description |
periodic_update_ms |
- |
+ |
Signal value will be published periodically according to the value set. |
DNP3.0 Master
Device sheet:
Parameter |
1.7.0 |
1.11 |
Description |
ip |
host |
ip |
use_local_time |
- |
+ |
If enabled (1), communication uses system time instead of UTC. |
DNP3.0 Slave
Device sheet:
Parameter |
1.7.0 |
1.11 |
Description |
|
Control_code |
- |
- |
DNP3 control model code of CROB signal. TripClose and Pulse control model requires PulseOn/off times to be set |
|
Pulse_on_time_ms |
- |
- |
Pulse ON time in milliseconds, when using Pulse or TripClose control models must be set |
|
Pulse_off_time_ms |
- |
- |
Pulse OFF time in milliseconds, when using Pulse or TripClose control models must be set |
|
IEC 101 Master
Device sheet:
Parameter |
1.7.0 |
1.11 |
Description |
broadcast_timesync |
- |
+ |
Enables or disables broadcast time sync. If 0 - disabled; if 1 - enabled. |
Signal sheet:
Parameter |
1.7.0 |
1.11 |
Description |
periodic_update_ms |
- |
+ |
Signal value will be published periodically according to the value set. |
tag_job_todo |
- |
+ |
tag_job_todo value must be: communication_status. If the signal returns 1 – connection is OK; if 2 – disconnected. |
IEC 101 Slave
Signal sheet:
Parameter |
1.7.0 |
1.11 |
Description |
periodic_update_ms |
- |
+ |
Signal value will be published periodically according to the value set. |
Select_ms |
- |
+ |
Polling interval in milliseconds. The time frame between two telegrams from the master. |
tag_job_todo |
- |
+ |
tag_job_todo value must be: communication_status. If the signal returns 1 – connection is OK; if 2 – disconnected. |
IEC 103 Master
Device sheet:
Parameter |
1.7.0 |
1.11 |
Description |
reset_command_type |
- |
+ |
The user can choose the reset command type between FCB and CU. |
Signal sheet:
Parameter |
1.7.0 |
1.11 |
Description |
periodic_update_ms |
- |
+ |
Signal value will be published periodically according to the value set. |
tag_job_todo |
- |
+ |
tag_job_todo value must be: communication_status. If the signal returns 1 – connection is OK; if 2 – disconnected. |
IEC 104 Master
Device sheet:
Parameter |
1.7.0 |
1.11 |
Description |
ip |
host |
ip |
Slave device IP |
Signal sheet:
Parameter |
1.7.0 |
1.11 |
Description |
periodic_update_ms |
- |
+ |
Signal value will be published periodically according to the value set. |
tag_job_todo |
- |
+ |
tag_job_todo value must be: communication_status. If the signal returns 1 – connection is OK; if 2 – disconnected. |
IEC 104 Slave
Signal sheet:
Parameter |
1.7.0 |
1.11 |
Description |
periodic_update_ms |
- |
+ |
Signal value will be published periodically according to the value set. |
tag_job_todo |
- |
+ |
tag_job_todo value must be: communication_status. If the signal returns 1 – connection is OK; if 2 – disconnected. |
IEC 61850 Server
Device sheet:
Parameter |
1.7.0 |
1.11 |
Description |
Tls |
+ |
- |
|
Edition |
+ |
- |
|
auth |
- |
+ |
Authorization type
|
authorization |
+ |
- |
|
IEC 61850 Client
Device sheet:
Parameter |
1.7.0 |
1.11 |
Description |
ip |
host |
ip |
|
auth |
- |
+ |
Authorization type
|
authorization |
+ |
- |
|
event_history_size |
+ |
- |
|
model_filename |
- |
+ |
The filename of the client model uploaded to WCC (must contain .client extension) |
MQTT
Device sheet:
Parameter |
1.7.0 |
1.11 |
Description |
ip |
host |
ip |
|
auth |
- |
+ |
Authorization type |
Ca_certificate |
- |
+ |
Certificate authority file for TLS connection |
Client_certificate |
- |
+ |
Client certificate file for TLS connection |
Client_key |
- |
+ |
The private key that corresponds to the client certificate for TLS connection |
Client_id |
- |
+ |
User-friendly name for client ID |
Signal sheet:
Signal |
1.7.0 |
1.11 |
Description |
periodic_update_ms |
- |
+ |
Signal value will be published periodically according to the value set. |
DLMS/COSEM
Device sheet:
Parameter |
1.7.0 |
1.11 |
Description |
poll_delay_ms |
+ |
- |
Minimum time delay in milliseconds to wait before sending any data on port. |
IEC 62056-21
Device sheet:
Parameter |
1.7.0 |
1.11 |
Description |
protocol_control_char |
- |
+ |
Protocol control character |
mode_control_char |
- |
+ |
Mode control character |
WCC Lite Internal Signals
Signal sheet:
Signal |
1.7.0 |
1.11 |
sim-select (gsm) |
- |
+ |
modem-reset (gsm) |
- |
+ |
New Services
Signal sheet:
Service |
1.7.0 |
1.11 |
Description |
Sms_receiver |
- |
+ |
SMS receiver is a service responsible for command execution that was received via text message. |