3 Technical information

System
Processor ARM CPU (AR9331, 400MHz)
Memory 16 MB Flash/64 MB DDR2 RAM
Wireless 802.11 b/g/n
I/O

1x Binary input (hardware version >=1.4)

1x Relay output

Additional storage SD card (2GB by default) SD card (2GB by default)
Ethernet 10/100 Base­T ­ RJ­45 connector up to 2 independent ports 10/100 Base­T ­ RJ­45 connector up to 2 independent ports
Serial ports 1x RS­485
1x RS­485 / RS­232 (switchable)
Time synchronization NTP client + server, IEC 60870­5­101, IEC 60870­5­104
GSM 2G(GPRS, EDGE) / 4G(LTE)
2G(GPRS, EDGE) / 3G(UMTS, HSDPA, HSUPA)
2G(GPRS, EDGE) / 3G(UMTS, HSDPA, HSUPA) / 4G(LTE)
Single OR Dual SIM card modem
Power requirements
Power supply  12 ­- 24 VDC
Power consumption  < 6W
Dimensions  101 (H) x 22.5 (W) x 119 (L), mm
Mounting  Wall mount, Din rail
Environmental
Operating temperature ­40°C to +85°C
Warranty  2 year
Humidity 2-95% RH (non-condensing)
Software
Compatibility with HMI (Human Machine Interface) Compatible with cloud-based SCADA system -CloudIndustries.eu
Routing • Isolated LAN interface
• Isolated LAN interface, but omitted to provide TCP / UDP ports or VPN mergers
• Routed LAN internet connection masking data for GSM interfaces
• Secure LAN data transfer via VPN
• Secure LAN data transmission through VPN access to the Internet
• Single OR Dual SIM card modem
Database • File-based database
• Data buffering in case of network outage
Data security • All data between WCC Lite and Cloud-based SCADA exchange over a secure encrypted VPN tunnel
• Firewall to prevent intrusion and DoS attacks
• A VPN solution with a VPN gateway can be used to manage (configure and update) and monitor VPN and WCC devices
from a single place
Device maintenance It is possible to configure and monitor devices and protocols connected to the WCC Lite through Elseta cloud-based SCADA system CloudIndustries.eu or 3rd party SCADAs and see device­based alarms such as communication errors, etc.
Supported protocols • Modbus master/slave (RTU / ASCII / TCP)
• M­Bus master (Serial / TCP)
• IEC 60870­5­ 101 master/slave
• IEC 60870­5­ 103 master
• IEC 60870­5­ 104 master/slave
• IEC 62056­31 master
• IEC 62056­21 (since v1.2.13)
• DNP3 master / slave
• SMA Net
• DLMS (since v1.3.0)
• Resol VBus
• IEC 61499 (since v1.4.0)
• IEC 61850 master/slave (since v1.5.0)
Supported devices • Other Elseta products
• Aurora PV inverters
• Delta inverters
• Kaco PV inverters
• SMA PV inverters
• Ginlong PV inverters
• Solplus PV inverters
• Kostal devices
• Windlog data logger
• Vestas Wind turbines
• Elgama elektronika electricity meters
Network features • IPsec
• OpenVPN
• xl2tp
• Firewall
• Routing
• RADIUS
• SNMP
• ser2net
• API
• NTP synchronization
Extra features • Software update
• Remote configuration via CloudIndustries.eu
administration
• Device fault notifications
• Internal web page for configuration and diagnostics