# 3 Technical information
##### System
ProcessorARM CPU (AR9331, 400MHz)
Memory16 MB Flash/64 MB DDR2 RAM
Wireless802.11 b/g/n
I/O1x Binary input (hardware version >=1.4) 1x Relay output
Additional storage SD card (2GB by default)SD card (2GB by default)
Ethernet 10/100 Base­T ­ RJ­45 connector up to 2 independent ports10/100 Base­T ­ RJ­45 connector up to 2 independent ports
Serial ports1x RS­485 1x RS­485 / RS­232 (switchable)
Time synchronizationNTP client + server, IEC 60870­5­101, IEC 60870­5­104
GSM2G(GPRS, EDGE) / 4G(LTE) 2G(GPRS, EDGE) / 3G(UMTS, HSDPA, HSUPA) 2G(GPRS, EDGE) / 3G(UMTS, HSDPA, HSUPA) / 4G(LTE) Single OR Dual SIM card modem
##### Power requirements
Power supply 12 ­- 24 VDC
Power consumption < 6W
Dimensions 101 (H) x 22.5 (W) x 119 (L), mm
Mounting Wall mount, Din rail
##### Environmental
Operating temperature­40°C to +85°C
Warranty 2 year
Humidity2-95% RH (non-condensing)
##### Software
Compatibility with HMI (Human Machine Interface)Compatible with cloud-based SCADA system -CloudIndustries.eu
Routing• Isolated LAN interface • Isolated LAN interface, but omitted to provide TCP / UDP ports or VPN mergers • Routed LAN internet connection masking data for GSM interfaces • Secure LAN data transfer via VPN • Secure LAN data transmission through VPN access to the Internet • Single OR Dual SIM card modem
Database• File-based database • Data buffering in case of network outage
Data security• All data between WCC Lite and Cloud-based SCADA exchange over a secure encrypted VPN tunnel • Firewall to prevent intrusion and DoS attacks • A VPN solution with a VPN gateway can be used to manage (configure and update) and monitor VPN and WCC devices from a single place
Device maintenanceIt is possible to configure and monitor devices and protocols connected to the WCC Lite through Elseta cloud-based SCADA system CloudIndustries.eu or 3rd party SCADAs and see device­based alarms such as communication errors, etc.
Supported protocols• Modbus master/slave (RTU / ASCII / TCP) • M­Bus master (Serial / TCP) • IEC 60870­5­ 101 master/slave • IEC 60870­5­ 103 master • IEC 60870­5­ 104 master/slave • IEC 62056­31 master • IEC 62056­21 (since v1.2.13) • DNP3 master / slave • SMA Net • DLMS (since v1.3.0) • Resol VBus • IEC 61499 (since v1.4.0) • IEC 61850 master/slave (since v1.5.0)
Supported devices• Other Elseta products • Aurora PV inverters • Delta inverters • Kaco PV inverters • SMA PV inverters • Ginlong PV inverters • Solplus PV inverters • Kostal devices • Windlog data logger • Vestas Wind turbines • Elgama elektronika electricity meters
Network features• IPsec • OpenVPN • xl2tp • Firewall • Routing • RADIUS • SNMP • ser2net • API • NTP synchronization
Extra features• Software update • Remote configuration via CloudIndustries.eu administration • Device fault notifications • Internal web page for configuration and diagnostics