Skip to main content

15.2 IEC 61850 Server

WCC Lite can act as an IEC 61850 server to serve data to remote SCADA systems. For example, WCC Lite can be used to acquire data from various protocols (Modbus, IEC 60870-5-103, etc.), this data can be redirected and propagated further to a single or multiple IEC 61850 clients. IEC 61850 Server supports TCP and TLS connection types. TCP connection can be secured with password authentication.

Commands

WCC Lite IEC 61850 Server implementation defines four command types which are described by their control model:

  • Case 1: Direct control with normal security (direct-operate);
  • Case 2: SBO control with normal security (operate-once or operate-many);
  • Case 3: Direct control with enhanced security (direct-operate);
  • Case 4: SBO control with enhanced security (operate-once or operate-many).

Normal security commands are considered for execution if the command signal is found in Excel configuration. There aren’t any additional checks in command execution in any master protocol.

Enhanced security commands need feedback from the master protocol to either succeed or fail. If feedback is not received within the command_ack_timeout_ms timeframe, the command is considered failed.

Command value attributes (e.g. stVal) must be updated separately (if they need to be updated).

When using SBO commands, select is not routed to the master protocol and select logic is performed only in IEC 61850 Server protocol.

Configuring data points

To use the IEC 61850 Server in WCC Lite, it has to be configured via an Excel configuration and the data model must be uploaded. This configuration contains two Excel sheets where parameters have to be filled in - Devices and Signals.

If a few devices were to connect to a server using the same virtual port, all of the IP addresses have to be specified on the host field separated by space. That way all of the clients will be able to connect from different IP addresses but using the same port as long as they all have the same subnet address. 

IEC 61850 Server parameters for Devices tab
Parameter

Type

Description

Required

Default value

(when not specified)

Range

Min

Max

name

string User-friendly name for a device Yes


description string Description of a device No


device_alias string Alphanumeric string to identify a device Yes


enable boolean Enabling/disabling of a device No 1 0 1
protocol string Protocol to be used Yes
IEC 61850 Server
bind_address string (IP address format) The IP address of an interface to use with the server No 0.0.0.0
host string (IP address format)

IP address list of allowed IPs (separated with spaces)

Yes


port integer

TCP communication port

No 102

auth string

Authorization type

Yes
“NONE”, “PASSWORD”, “TLS”
password string

Authorization password for server device

Yes ( for PASSWORD)

tls_local_certificate string

Local certificate for TLS connection

Yes (for TLS)

tls_peer_certificate string Certificate authority file for TLS connection Yes (for TLS)

tls_private_key string A file consisting of the private key for TLS connection Yes (for TLS)


ied_name string Name of an Intelligent Electronic Device Yes


originator string Origin identification for the device No


model_filename string The filename of the server model, without the .server extension Yes


command_ack_timeout_ms

integer

Timeframe (ms) in which enhanced security commands must be acknowledged

(Default: 3000)

No 3000

report_buffered_size integer

Report control blocks buffer size in bytes

(Default: 65536)

No 65536

report_unbuffered_size integer

Unbuffered report control blocks buffer size in bytes (Default: 65513)

No 65513

IEC 61850 Server parameters for Signals tab
Parameter

Type

Description

Required

Default value

(when not specified)

Range

Min

Max

signal_name string User-friendly signal name Yes


device_alias string Device alias from a Devices tab Yes


signal_alias string Unique alphanumeric name of the signal to be used Yes


enable boolean Enabling/disabling of an individual signal No 1 0 1
log boolean Allow signal to be logged. If the log is 0 signal will not be logged. If the log is more than 0 signal will be logged No 0

number_type string Number format type (BOOLEAN, FLOAT, INT16, etc.) Yes
BOOLEAN, INT8, INT16, INT32, INT64, INT128, INT8U, INT24U, INT32U, FLOAT32, FLOAT64, ENUMERATED, OCTET STRING 64, OCTET STRING 6, OCTET STRING 8, VISIBLE STRING 32, VISIBLE STRING 64, VISIBLE STRING 65, VISIBLE STRING 129, VISIBLE STRING 255, UNICODE STRING 255, TIMESTAMP, QUALITY, CHECK, CODEDENUM, GENERIC BITSTRING, CONSTRUCTED, ENTRY TIME, PHYCOMADDR, CURRENCY, OPTFLDS, TRGOPS
ld_instance string An instance of a logical device Yes


ln_class string Logical node class type Yes


ln_instance integer An instance of a logical node  No


ln_prefix string Prefix of logical node string No


cdc string Common Data Class (CDC) name Yes
SPS, DPS, INS, ACT, ACD, SEC, MV, CMV, WYE, DEL, SEQ, SPG, ING, ASG, ENS, ENG
data_object string Name of a data object in the dataset Yes


da_value string Name of a data attribute value node Yes


da_fc string Functional constrain for data object Yes
ST, MX, CO, SP
control_model

string

Model of output control

Yes (for commands)

read-only

read-only,

direct-with-normal-security,

sbo-with-normal-security,

direct-with-enhanced-security, sbo-with-enhanced-security

Device status signals
 

IEC 61850 has an additional signal which can be configured to show communication status. It is used to indicate if the client device has disconnected from the server (WCC Lite). To configure such a signal for the IEC 61850 protocol, job_todo and tag_job_todo fields with string values are required. For the IEC 61850 server required parameters for the status signal will be signal_name device_alias, signal_alias, number_type, job_todo and tag_job_todo. Job_todo value must be device_status and for tag_job_todo there are 4 variations: communication_status, device_running, device_error, uknown_error. Each signal has 4 possible values and is based on the same logic. If the signal returns the value of 0, it means an unknown error has appeared, 1 – device or protocol connection is on and working properly, 2 – device is off or protocol is disconnected, 3 – error or service is down.

Converting and uploading data model

To use the IEC61850 Server protocol in WCC Lite, the user must upload a data model in a specific format (file extension .server). These data models can be converted from SCL files (.icd, .cid or .scd files). To convert a data model, the user must use WCC Excel Utility. There’s a separate tab for this operation as shown in the picture below.

image-1670582144161.png

The converted file can be uploaded in the WCC Lite web interface, Protocol Hub section. The current model can be also downloaded on the same page as shown in the picture below.

image-1670583136986.png

Debugging an IEC 61850 server application

If the configuration for the IEC 61850 Server is set up, a handler for the protocol will start automatically. If the configuration is missing or contains errors, the protocol will not start. It is done intentionally to decrease unnecessary memory usage.

If the IEC 61850 Server does not work properly (e.g. no communication between devices, data is corrupted, etc.), a user can launch a debug session from the command line interface and find out why the link is not functioning properly.

To launch a debugging session, a user should stop iec61850-server process and run iec61850-server command with respective flags as you can see below:

iec61850-server
-h [--help] Show help message
-c [--config] arg Configuration file location
-V [--version] Show version
-d [--debug] arg Set Debug level
-r [--redis] Show Redis messages
-C [--commands] Show command messages
-R [--readyfile] arg Ready notification file