13.3 Modbus Slave
WCC Lite can act as one (or several) of slave devices in a communication line. This can be used to transmit data to SCADA systems or other RTU devices. It can reply to a messages from Modbus Master with matching device and register addresses.
Configuring datapoints
To use Modbus Slave in WCC Lite, it has to be configured via an Excel configuration. This configuration contains two Excel sheets where parameters have to be filled in - Devices and Signals
If TCP/IP is used as a trasmission medium, only devices with IPs predefined in host column are allowed to connect. All other connections are rejected
Modbus Slave parameters for Devices tab
Parameter |
Type |
Description |
Required |
Default value (when not specified) |
Range |
|
Min |
Max |
|||||
name |
string |
User-friendly name for a device |
Yes | |||
description |
string |
Description of a device |
No | |||
device_alias |
string |
Alphanumeric string to identify a device |
Yes | |||
enable | boolean |
Enabling/disabling of a device |
No | 1 | 0 | 1 |
protocol | string |
Protocol to be used |
Yes | Modbus serial Slave, Modbus TCP Slave | ||
host | string | Space separated host IP addresses of master device |
Yes (for TCP). | |||
port | integer |
TCP port to listen for incoming connections |
Yes (for TCP) |
|
|
|
bind_address | string |
IP address of network adapter used to connect to slave device (Default: ”0.0.0.0”) |
No (for TCP) | 0.0.0.0 | ||
keep_alive_timeout |
integer |
Minimum time a connection can be idle without being closed in miliseconds |
No (for TCP) | 60 | ||
mode | string | Choosing between RTU (”rtu”), ASCII (”ascii”) and TCP(”tcp”) modes. ASCII is the same as RTU, but with ASCII symbols. |
No |
TCP (for TCP) RTU (for Serial) |
rtu, ascii, tcp | |
device |
string |
Communication port (”PORT1”/”PORT2”) |
Yes (for serial) |
|
PORT1 |
PORT2 |
baudrate | integer |
Communication speed, baud/s |
No (for serial) |
9600 |
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 |
|
databits | integer |
Data bit count for communication |
No (for serial) |
8 |
6 |
9 |
stopbits | integer |
Stop bit count for communication |
No for serial) |
1 |
1 |
2 |
parity |
string |
Communication parity option |
No (for serial) |
none |
none, even, odd |
|
flowcontrol |
string |
Communication device’s flow control |
No (for serial) |
none |
none |
Modbus Slave parameters for Signals tab
Parameter |
Type |
Description |
Required |
Default value (when not specified) |
Range |
|
Min |
Max |
|||||
signal_name |
string |
User-friendly signal name |
Yes | |||
device_alias |
string |
Alphanumeric string to identify a device |
Yes | |||
signal_alias |
string |
Unique alphanumeric name of the signal to be Yes used |
Yes | |||
enable | boolean |
Enabling/disabling an individual signal |
No | 1 | 0 | 1 |
number_type |
string |
Type of a number (FLOAT, DOUBLE, DIGITAL, etc.). This defines the size that will be read. |
Yes | |||
log |
integer |
Size of this signal’s log in the Event log. |
No | 0 | ||
slave_id | integer | Address of a slave device | Yes | |||
function | integer | Function number | Yes | |||
register_address | integer | Register address | Yes |
Modbus Slave has an additional signal which can be configured to show communication status. It is used to indicate if the slave device has disconnected from the master or vice versa. To configure such a signal, one column should be filled with particular value. To create an additional signal, one should make a tag_job_todo
column equal to device_status
or communication_status. Communication error status is set when a predefined count of messages (three by default, defined in keep_alive_timeout
column) fail to be received or are considered invalid.
Mapping values to registers
Internally stored values aren’t organised in a register-like order, therefore mapping should be done by the user. This mapping includes setting an address of the device WCC Lite is simulating as well as function number, register number and how much 16-bit registers are used to store a value. These values should be set in common_address
, function
, info_address
and size
columns respectively in the Excel configuration.
To find out how many register should be used for storing a values, how values can have their values swapped, a user should consult a section number_type
(18.2.4).
If a Modbus master device requests a data from a register that is mapped but doesn’t yet have initial value, ILLEGAL DATA ADDRESS error code will be returned. The same error code is returned if a requested size of value is bigger that defined or if register is not configured at all.
Debugging a Modbus Slave application
If configuration for Modbus Slave is set up, handler for protocol will start automatically. If configuration is missing or contains errors, protocol will not start. It is done intentionally to decrease unnecessary memory usage.
Modbus Slave command line debugging options
modbus-slave
-h [ –help ] Display help information
-V [ –version ] Show version
-d<debug level> Set debugging level
-c [ –config ] Config path
-r [ –raw ] Show raw telegram data
-f [ –frame ] Show frame data
-s [ –serial ] Show serial port data
–tcp Show tcp packets
–ascii Show ASCII messages
–rtu Show RTU messages
-e [ –redis ] Show redis debug information
-R [ –readyfile ] Ready notification file
If Modbus Slave does not work properly (e.g. no communication between devices, data is corrupted, etc.), a user can launch a debug session from command line interface and find out why link is not functioning properly.
To launch a debugging session, a user should stop modbus-slave
process and run modbus-slave
command with respective flags as shown above.