Skip to main content

15 Elgama

Overview

Elgama protocol is used for communications with Elagama elektronika electricity meters.

Configuration

Available meter types (use number only):

  • 0 ­ EPQM/LZQM
  • 1 ­ EPQS
  • 2 ­ GAMA300
  • 3 ­ GAMA100
  • 4 ­ ITS cl
Elgama parameters for Device tab
Parameter

Type

Description

Required

Default value

(when not specified)

Range

Min

Max

name string  User-friendly device name Yes

 

 

 

description string Description of a device No

 

 

 

device_alias string Alphanumeric string to identify a device Yes      
enable boolean Enabling/disabling of a device No 1 0 1
protocol string Protocol to be used. Yes  

Elgama

device string Communication port Yes   PORT1 PORT2
baudrate integer Communication speed, bauds/s No 9600 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600,115200
serial_close_delay integer Delay before closing serial port in milliseconds No 400    
timeout_ms integer Timeout of waiting for incoming request in milliseconds Yes      
id integer Meter serial number Yes      
meter_model integer Meter type (See 15.2) Yes   0 4
use_time boolean Use system/meter (0/1) time (Default: 0) No 0 0 1
Elgama parameters for Signals tab
Parameter

Type

Description

Required

Default value

(when not specified)

 

Range
Min Max
signal_name

string

User-­friendly signal name

Yes  

 

 

device_alias

string

Device alias from a Devices tab

Yes  

 

 

signal_alias

string

Unique alphanumeric name of the signal to be used

Yes  

 

 

enable

boolean

Enabling/disabling of an individual signal

No 1

0

1

log

integer

Enable logging in event log

No 0

 

 

number_type string Type of number (FLOAT, DOUBLE, DIGITAL, etc.) Yes      
job_todo

string

Tag job as single or multiple comma separated OBIS codes

Yes  

 

 

tag_job_todo string Tag sub job Yes