15 Elgama
Overview
Elgama protocol is used for communications with Elagama elektronika electricity meters.
Configuration
Available meter types (use number only):
- 0 EPQM/LZQM
- 1 EPQS
- 2 GAMA300
- 3 GAMA100
- 4 ITS cl
Elgama parameters for Device tab
Parameter |
Type |
Description |
Required |
Default value (when not specified) |
Range |
|
Min |
Max |
|||||
name | string | User-friendly device name | Yes |
|
|
|
description | string | Description of a device | No |
|
|
|
device_alias | string | Alphanumeric string to identify a device | Yes | |||
enable | boolean | Enabling/disabling of a device | No | 1 | 0 | 1 |
protocol | string | Protocol to be used. | Yes |
Elgama |
||
device | string | Communication port | Yes | PORT1 | PORT2 | |
baudrate | integer | Communication speed, bauds/s | No | 9600 | 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600,115200 | |
serial_close_delay | integer | Delay before closing serial port in milliseconds | No | 400 | ||
timeout_ms | integer | Timeout of waiting for incoming request in milliseconds | Yes | |||
id | integer | Meter serial number | Yes | |||
meter_model | integer | Meter type (See 15.2) | Yes | 0 | 4 | |
use_time | boolean | Use system/meter (0/1) time (Default: 0) | No | 0 | 0 | 1 |
Elgama parameters for Signals tab
Parameter |
Type |
Description |
Required |
Default value (when not specified)
|
Range | |
Min | Max | |||||
signal_name |
string |
User-friendly signal name |
Yes |
|
|
|
device_alias |
string |
Device alias from a Devices tab |
Yes |
|
|
|
signal_alias |
string |
Unique alphanumeric name of the signal to be used |
Yes |
|
|
|
enable |
boolean |
Enabling/disabling of an individual signal |
No | 1 |
0 |
1 |
log |
integer |
Enable logging in event log |
No | 0 |
|
|
number_type | string | Type of number (FLOAT, DOUBLE, DIGITAL, etc.) | Yes | |||
job_todo |
string |
Tag job as single or multiple comma separated OBIS codes |
Yes |
|
|
|
tag_job_todo | string | Tag sub job | Yes |