Skip to main content

17.3 Elgama

Overview

Elgama protocol is used for communications with Elgama elektronika electricity meters.

Configuration

Available meter types (use number only):

  • 0 ­ EPQM/LZQM
  • 1 ­ EPQS
  • 2 ­ GAMA300
  • 3 ­ GAMA100
  • 4 ­ ITS cl
Elgama parameters for Device tab
Parameter

Type

Description

Required

Default value

(when not specified)

Range

Min

Max

name string  User-friendly device name Yes

 



description string Description of a device No

 



device_alias string Alphanumeric string to identify a device Yes


enable boolean Enabling/disabling of a device No 1 0 1
protocol string Protocol to be used. Yes

Elgama

device string Communication port Yes
PORT1 PORT2
baudrate integer Communication speed (bauds/s) No 9600 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600,115200
serial_close_delay integer Delay before closing serial port in milliseconds No 400

timeout_ms integer Timeout of waiting for incoming request in milliseconds Yes


id integer Meter serial number Yes


meter_model integer Meter type  Yes
0 4
use_time boolean Use system/meter (0/1) time (Default: 0) No 0 0 1
Elgama parameters for the Signals tab
Parameter

Type

Description

Required

Default value

(when not specified)

Range

Min

Max

signal_name

string

User-­friendly signal name

Yes



device_alias

string

Device alias from a Devices tab

Yes



signal_alias

string

Unique alphanumeric name of the signal to be used

Yes



enable

boolean

Enabling/disabling of an individual signal

No 1

0

1

log

integer

Enable logging in event log

No 0



number_type string Type of number (FLOAT, DOUBLE, DIGITAL, etc.) Yes


job_todo

string

Elgama protocol specific data set values  (see files below) Yes



tag_job_todo string Tag sub job Yes


Files

  1. Example configuration file for Elgama protocol data mapping download