16.3 COMLYNX

Overview

Comlynx protocol is used to communicate with Comlynx inverters over serial communication.

Comlynx parameters for Device tab:
Parameter

Type

Description

Required

Default value

(when not specified)

Range

Min

Max

name string User-friendly device name Yes


description string Description of the device No


device_alias string Device alias to be used in configuration Yes


enable boolean Enabling/disabling of a device No 1 0 1
protocol string Selection of protocol Yes
Comlynx
address integer Device address No 1
subnet integer Subnet address No 0
network integer Network address No 0
device string Communication port Yes
PORT1 PORT2
baudrate integer Communication speed, bauds/s No 19200 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
databits integer Data bit count for communication No 8 6 9
stopbits integer Stop bit count for communication No 1 1 2
parity string Communication parity option
(”none”/”even”/”odd”)
No none

flowcontrol string Communication device flow control option. (Default: (case-sensitive): ”none”) No none

scan_rate_ms integer If provided and positive ­ all reads and writes will be executed within the timeframe in miliseconds. No 10000

poll_delay_ms integer Minimum time delay in miliseconds to wait before sending any data on port. No 200

timeout_ms integer Timeout in milliseconds Yes
0 60000


Comlynx parameters for Signals tab:
Parameter

Type

Description

Required

Default value

(when not specified)

Range

Min

Max

signal_name string User-friendly device name Yes


device_alias string Device alias from a Devices tab Yes


signal_alias string Unique alphanumeric name of the signal to be used Yes


enable boolean Enabling/disabling of an individual signal No 1 0 1
log integer Allow signal to be logged. No 0

job_todo boolean Define tag­-function Yes


tag_job_todo string Define tag action that depends on tag function Yes


number_type integer Type of a number (FLOAT, DOUBLE, DIGITAL, etc.) Yes


pulse_short_time_ms integer Time interval for short output pulse to stay active No 0

pulse_long_time_ms integer Time interval for long output pulse to stay active No 0