IOMOD models and types
The IOmod series comprises devices that incorporate various input and output modules. These modules all operate using one of three firmware versions (except for 4Cs4Vs, which uses one of two). These firmware versions serve to distinguish the communication protocols utilized via the RS485 interface. Importantly, all types of IOmod devices employ the same firmware and do not necessitate specific firmware for their respective types. IOmod devices are designed with the capability to automatically identify the hardware type and determine the supported functions.
IOmod finds utility in industrial settings where digital signaling and robust communication are essential. It serves as an ideal solution for applications like data acquisition, control, and process monitoring, particularly in scenarios requiring remote access.
IOmod type | Inputs | Outputs | Power supply | Supported functions |
IOMod 8DI8DO | 8x DI (12-24 DC)* | 8x DO ( open collector outputs ) | 12-24 VDC |
Digital inputs readings with time resolution 1ms; Commands execution; |
IOMod 16DI | 16x DI (12-24 DC)* | - | 12-24 VDC |
Digital inputs readings with time resolution 1ms; Pulse counter (in modbus RTU) |
IOMod 8AI | 8x AI (±10 VDC // ±20 mA) including ranges (0..10 VDC, 0..20 mA, 4..20 mA) 16bit ADC | - | 12-24 VDC |
Analog inputs readings: 0..10V (DC); 0..20mA (DC); 4..20mA (DC) |
IOMod 4RTD | 4x RTD (PT100; PT1000) including 2,3,4 sensor wiring. | - | 12-24 VDC |
Temperature readings; |
IOMod 8DI4RO |
8x DI (12-48 VDC)* |
4x Relay outputs (5 A; 250 VAC) |
12-24 VDC |
Digital inputs readings with time resolution 1ms; Commands execution; |
IOMod 4Cs4Vs |
4x AC current inputs (225 mV) 4x AC voltage inputs (3.25 V/√3) |
- |
12-24 VDC |
Current readings; Voltage readings; |
IOMod HT | Ambient temperature -30C ..+ 80C; Humidity 20..100% | - | 12-24 VDC |
Temperature readings; Humidity readings; |
IOMod HT(advanced) | Ambient temperature -30C ..+ 80C; Humidity 20..100% | 2x Relay outputs (2 A; 250 VAC) | 12-24 VDC |
Temperature readings; Humidity readings; Remote relay control; Relay control based on temperature; Relay control based on humidity. |
* - on request can be delivered IOmod modules with input voltages for 48VDC and 110VDC power systems.