23 Data Export General Various protocols are made to transmit data points as they are generated. This is enough for a lot of systems (e.g. SCADAs) that have their own databases and devices only have to buffer fairly recent messages in case of connection or transmission errors. However, there is frequently a need to save and keep the data in files, grouped in batches, and later transmit these batches to a remote server via HTTP(S) or FTP(S). For this purpose a dedicated protocol has been created and called Data export. Data export functionality is available since firmware version v1.5.0, of WCC Lite. Overview Data export service gathers information from other protocols, puts it into files (optionally compressing them) after a timeout or when data buffers fill up; eventually periodically sending them to a server. HTTP(S) and FTP(S) servers with optional authentication are supported. A user can optionally choose between ISO8601 and UNIX timestamp time formats (the latter being the default value). More than one instance can set up, for instance, some of the information can be sent to an FTP server, while other could be transmitted to the HTTP server which is able to handle POST requests. Using WCC Lite for data export To configure WCC Lite to use data export server a user can fill in the needed parameters in Excel configuration. These parameters are shown in two tables below. Default values are shown in a bold font. Data export (data-export) parameters for Devices tab table: Parameter Type Description Required Default value (when not specified) Range Min Max name string User-friendly device name Yes device_alias string Device alias to be used in configuration Yes enable boolean Enabling/disabling of a device No 1 0 1 protocol string Selection of protocol Yes Data Export timeout integer Time frame during which transmission to remote server has to be completed (in seconds) No 5 type string Selection of file format No csv-simple cvs-periodic csv-simple, json-simple, json-samples host string A URL of remote server where files should be sent Yes upload_rate_sec integer Frequency of generated file uploads (in seconds) No 60 records_buffer_size integer A maximum amount of data change entries to hold before initiating logging mechanism No 100 logging_period_sec integer Describes how frequently data buffer of records_buffer_size is saved to file No 10 1 3600 log_folder string A folder in WCC Lite file system to save generated file (”/var/cache/data-export”) No timestamp string Selection of time format No unixtimestamp unixtimestamp, iso8601 compress string Selection of file compression mechanism No none none, gz, tar.gz compress_password string Enable feature of file password protection No yes, true csv_field_separator string Columns separator in .csv file format No "," - (comma) "," - (comma) ";" - (semicolon) "." - (dot) " " - whitespace) "|" - (pipe) csv_decimal_separator string Decimal separator in values No "." - (dot) "." - (dot) "," - (comma) Same symbols cannot be selected for both csv_field_separator and csv_decimal_separator. In such case both of them will be set to default values ­ ”.” and ”,” respectively. It is possible that data generation rate is going to be bigger than what data buffer can hold (controlled by records_buffer_size and logging_period_sec). To make sure that no data loss occurs there’s an additional data logging call made in case data buffer reaches a records_buffer_size value. Signals to be sent are configured differently than signals for most other protocols. As data export service only transmits signals and does no data processing, usual signal logic is not used for them. That means that: • Signals for data export service are not seen in the Imported Signals tab;• Signals for data export service are configured in different Excel sheet called DataExport Parameters to be filled in the DataExport sheet are shown in a table below. Data export (data-export) parameters for DataExport tab Parameter Type Description Required Default value (when not specified) Range Min Max device_alias string Device alias to be used in configuration Yes Yes device_name string User friendly device name as in Device sheet Yes tag_name string User friendly signal name Yes source_device_alias string device_alias of a source device Yes source_signal_alias string source_alias of a source signa Yes enable boolean Enabling/disabling of a measurement to be transmitted and logged No 1 0 1 attribute string Additional attribute to be attached to a signal No Debugging data export service If configuration for Data export service is set up, handler for protocol will start automatically. If configuration is missing parameters or contains errors, protocol will not start. It is done intentionally to decrease unnecessary memory usage. Data export (data-export) command-line debugging options The below-described parameters for debugging are accessible over console (SSH). -h [--help] Display help information -c [--config] Configuration file location -V [ –version ] Show version -d [ –debug ] Set debugging level -R [ –readyfile] Ready notification file -p [ –http ] Show HTTP messages -r [ –redis ] Show Redis output If Data export service does not work properly (e.g. data is corrupted, etc.), a user can launch a debug session from command line interface and find out why it is not functioning properly. To launch a debugging session, a user should stop data-export processes and run data-export command with respective flags as in table above. Host URL format rules Parameter host is highly configurable and might contain a considerable amount of information: • Protocol - FTP or HTTP (encrypted and encrypted); • URL address - both resolved and non-resolved; • Authentication - pair of user and/or password; • Port - useful when non-standard value is used; • Endpoint - a place in server to which a call is made The format for host parameter can be summarized as: [ h t t p ( s ) / f t p ( s ) ] : / / [ [ u s e r ] : [ p a s s w o r d ]@] [ URL ] [ : p o r t ] / [ e n d p o i n t ] Options are printed in square brackets. A protocol has to be selected, otherwise HTTP will be used as a default. User and password pair is optional, but if user: password pair is used, it should proceeded with @ sign. HTTP and FTP use default or user assigned ports. By default HTTP uses port 80, while HTTPS uses port 443, FTP sends data over port 21, FTPS - over port 990. Make sure that these ports are open in firewall on both server and client side, otherwise data will not be sent successfully. Finally, POST request (for HTTP) or upload (for FTP) can be made to a specific place (endpoint). This endpoint should be described after a URL and port (if used). Format of exported data For a server to interpret data, a set of rules for a file format have to be established. Csv-simple format applies to all files by default and is used as in this example: ###DUID:3182121xx #device name; tag name; value; quality; timestamp; atribute inv1;Ia;236.9,1;1599137189963;Pa Example of additional format csv-periodic: ###DUID:318212xxx ##DEVICE:inv1 #Time;Upv1;Upv2;Upv3;Upv4;Upv5;Upv6;Ipv1;Ipv2;Ipv3;Ipv4;Ipv5;Ipv6;Status;Error;Temp;cos;fac;Pac;Qac;Eac;E-Day;E-Total;Cycle Time 2020-09-02T15:45:00Z;462.3;462.3;370.2;370.2;371.2;371.2;1.40;1.43;1.35;1.47;1.21;1.26;512;0;26.3;1.000;50.00;3.217;-0.029;0.28;17.41;54284.53;5; 2020-09-02T15:40:00Z;462.3;462.3;370.2;370.2;371.2;371.2;1.40;1.43;1.35;1.47;1.21;1.26;;512;0;26.3;1.000;50.00;3.217;-0.029;0.28;17.41;54284.53;5; ##DEVICE:meter #Time;Uab;Ubc;Uca;P;Q;S;F;eTOT;Cycle Time 2020-09-02T15:45:00Z;421.3;421.3;421.3;15000;100;15600;50;246894;5; 2020-09-02T15:40:00Z;421.3;421.3;421.3;15000;100;15600;50;246895;5; Example of additional format json-simple: { "metadata": { "duid": "318xxxxx", "name": "hostname", "loggingPeriod": "15min", "format": "json" }, "data": [ { "tag_name": "Ia", "device_name": "inv1", "attribute": "Pa", "last": { "value": 12.2, "timestamp": 1213123 }, "min": { "value": 12, "timestamp": 1213123 }, "max": { "value": 12, "timestamp": 1213123 }, "avg": { "value": 12, "timestamp": 1213123 } }, { "tagName": "Ib", "deviceName": "inv1", "attribute": "Pb", "last": { "value": -12.3, "timestamp": 1213123 }, "min": { "value": 12, "timestamp": 1213123 }, "max": { "value": 12, "timestamp": 1213123 }, "avg": { "value": 12, "timestamp": 1213123 } }, ] } Example of additional format json-sample: { "metadata": { "duid": "318xxxxx", "name": "hostname", "loggingPeriod": "15min", "format": "json-samples" }, "data": [ { "tag_name": "Ia", "device_name": "inv1", "attribute": "Pa", "timestamp":{ "first": 123123, "last": 123236 }, "first": { "value": 12.2, "timestamp": 1213123 }, "last": { "value": 12.2, "timestamp": 1213123 }, "min": { "value": -12, "timestamp": 1213123 }, "max": { "value": 12, "timestamp": 1213123 }, "avg": { "value": 12, "timestamp": 1213123 }, "samplesCount": 2, "samples": [ {"value": 12, "timestamp": 1213123, "quality": true}, {"value": -12.3, "timestamp": 1213123, "quality": true} ] } ] }