16.9 SOLPLUS Overview Solplus protocol is used to download inverter data from Solplus inverters using a HTTP client. Configuration Solplus parameters for Device tab Parameter Type Description Required Default value (when not specified) Range Min Max name string User-friendly device name Yes description string Description of a device No device_alias string Alphanumeric string to identify a device Yes enable boolean Enabling/disabling of a device No 1 0 1 protocol string Protocol to be used. Yes Solplus scan_rate_ms integer All reads and writes will be executed within the timeframe in milliseconds No 10000 poll_delay_ms integer Minimum time delay in milliseconds to wait before sending any data on port. No 200 timeout_ms integer Timeout of waiting for incoming request in milliseconds No 2500 0 60000 url string HTTP server location URL Yes Solplus parameters for Signals tab Parameter Type Description Required Default value (when not specified) Range Min Max signal_name string User-­friendly signal name Yes device_alias string Device alias from a Devices tab Yes signal_alias string Unique alphanumeric name of the signal to be used Yes enable boolean Enabling/disabling of an individual signal No 1 0 1 log integer Enable logging in event log No 0 number_type string Type of a number (FLOAT, DOUBLE, DIGITAL, etc.) Yes job_todo string Tag job as single or multiple comma separated OBIS codes Yes tag_job_todo string Tag sub job Yes pulse_short_time_ms integer Time interval for short output pulse to stay active No 0 pulse_long_time_ms integer Time interval for long output pulse to stay active No 0