# 14.3 IEC 60870-5-101 Slave ### Configuring datapoints (slave) The IEC 60870-5-101 Slave in WCC Lite has to be configured in Excel. This configuration contains two Excel sheets where parameters must be filled in *Devices* and *Signals.* ##### *IEC 60870-5-101 slave parameters for Devices tab*
**Parameter | **Type | **Description | **Required | **Default value** (when not specified) | **Range** | |
Min | Max | |||||
name | string | User-friendly name for a device | Yes | |||
description | string | Description of a device | No | |||
device\_alias | string | Alphanumeric string to identify a device | Yes | |||
enable | boolean | Enabling/disabling of a device | No | 1 | 0 | 1 |
protocol | string | Protocol to be used | Yes | IEC 60870-5-101 slave | ||
device | string | Communication port | Yes | PORT1 | PORT2 | |
baudrate | integer | Communication speed (bauds/s) | No | 9600 | 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 | |
databits | integer | Data bit count for communication | No | 8 | 6 | 9 |
stopbits | integer | Stop bit count for communication | No | 1 | 1 | 2 |
parity | string | Communication parity option | No | none | none, even, odd | |
flowcontrol | string | Number of requests, before the link is considered lost (device status signals are changed) and reconnect attempt will be issued | No | none | none | |
link\_address | integer | Destination address when in transmit and source address when broadcasting | Yes | 0 | 65535 | |
link\_size | integer | Link address size in bytes | No | 1 | 1 | 2 |
asdu\_size | integer | Common address size in bytes | No | 1 | 1 | 2 |
ioa\_size | integer | Information object address (IOA) size in bytes | No | 2 | 1 | 3 |
cot\_size | integer | Cause of transmission (COT) size in bytes | No | 1 | 1 | 2 |
time\_sync | boolean | Allow time synchronization, 1 to enable and 0 to disable | Yes | 0 | 1 | |
message\_size | integer | Maximum length of a message | No | 253 | 0 | 255 |
cache\_size | integer | Maximum number of events to store in a buffer | No | 100 | 0 | 1000 |
respond\_delay | integer | Time in microseconds to wait before sending responses | No | 100 | 0 | 1000000 |
single\_byte\_ack | boolean | Use single character acknowledge, 1 to enable and 0 to disable | No | 0 | 0 | 1 |
keep\_alive\_timeout | integer | Time interval in seconds before serial connection is considered offline | No | 60 |
**Parameter | **Type | **Description | **Required | **Default value** (when not specified) | **Range** | |
Min | Max | |||||
signal\_name | string | User-friendly signal name | Yes | |||
device\_alias | string | Alphanumeric string to identify a device | Yes | |||
signal\_alias | string | Unique alphanumeric name of the signal to be Yes used | Yes | |||
source\_device\_alias | string | device\_alias of a source device | For commands | |||
source\_signal\_alias | string | signal\_alias of a source signal | For commands | |||
enable | boolean | Enabling/disabling of an individual signal | No | 1 | 0 | 1 |
log | integer | Allow signal to be logged. If the **log is 0, the signal** will not be logged. If the **log is more than 0, the** signal will be logged | No | 0 | ||
gi | boolean | Including/excluding (1 or 0) signals from General Interrogation | No | 0 | 0 | 1 |
common\_address | integer | Address of a destination device | Yes | |||
info\_address | integer | Information object address | Yes | |||
data\_type | integer | ASDU type identifier | Yes | 1, 2, 3, 4, 5, 6, 9, 10, 11, 12, 13, 14, 30, 31, 32, 34, 35, 36, 45, 46, 47, 48, 49, 50, 58, 59, 60, 61, 62, 63 | ||
periodic\_update\_ms | integer | Signal value is published periodically according to the value set. | No | - | - |