# Modbus RTU to DNP3 protocol conversion ## Setup
The article describes WCC Lite configuration steps to enable Modbus RTU protocol conversion to DNP3 serial. [![image-1744184546840.png](https://wiki.elseta.com/uploads/images/gallery/2025-04/scaled-1680-/image-1744184546840.png)](https://wiki.elseta.com/uploads/images/gallery/2025-04/image-1744184546840.png) Before you begin, make sure you have completed all physical installation work according to the manufacturer's installation instructions. Set up your computer and connect the Ethernet cable to the WCC Lite ETH0 port. Log in with default credentials and set up basic required settings (name, network, users, etc.). You can find configuration tutorials in [How to](https://wiki.elseta.com/books/how-to) articles. To prepare the configuration, fill in the information in both the [Devices ](https://wiki.elseta.com/books/how-to/page/dlms-serial-to-iec104-protocol-conversion#bkmrk-configure-devices)and [Signals](https://wiki.elseta.com/books/how-to/page/dlms-serial-to-iec104-protocol-conversion#bkmrk-configure-signals) sheets: ## Configuring Devices ##### Add a connected ABB meter with the Modbus RTU protocol required information:
**name****description****device\_alias****enable****protocol****id****device****baudrate****databits**
From ABB MeterABB B21B211Modbus RTU1PORT196008
**stopbits****parity****flowcontrol****scan\_rate\_ms****serial\_delay****retry\_count**
1nonenone50002003
##### Add the SCADA working on the DNP3 protocol required information:
**name****device\_alias****enable****protocol****mode****bind\_address**
DNP3DNP3\_SCADA1DNP3 TCP slaveTCP0.0.0.0
**host****port**source\_address unsol\_classes
192.168.1.1 2000011,2,3
You can find more options and descriptions of the settings in the [Device configuration](https://wiki.elseta.com/books/excel-configuration/page/device-configuration "Device configuration") article. ## Configuring Signals Add connected meter measurements information. Use the meter manual for information and addresses (**tag\_job\_todo).**
**signal\_name****device\_alias****signal\_alias****enable****multiply****log****job\_todo****tag\_job\_todo****number\_type**
VoltageB21U10.113;23296;23;23296;2UNSIGNED32
CurrentB21I10.0113;23308;23;23308;2UNSIGNED32
Active powerB21P10.0000113;23316;23;23316;2SIGNED32
FrequencyB21F10.0113;23340;13;23340;1UNSIGNED16
Power factorB21Cos10.00113;23354;13;23354;1SIGNED16
Active importB21E10.0113;20480;43;20480;4FLOAT

**job\_todo** -Request to send according to Modbus specification without device address and checksum;

**tag\_job\_todo** - a subset of the **job\_todo** field, exact address of measurement (tag)

Add **DNP3** master signals information:
**signal\_name****device\_alias****signal\_alias****source\_device\_alias****source\_signal\_alias**
Voltagednp3dnp3\_1001B21U
Currentdnp3dnp3\_1002B21I
Active powerdnp3dnp3\_1003B21P
Frequencydnp3dnp3\_1004B21F
Power factordnp3dnp3\_1005B21Cos
Active importdnp3dnp3\_1006B21E
**enable****log****index****signal\_type****static\_variation****event\_variation****class\_num**
111analog1113
112analog1113
113analog1113
114analog1113
115analog1113
116analog1113
## Uploading the Configuration After configuring all devices and signals, follow these steps to check and upload the configuration using the WCC Excel Utility: 1. [Download ](https://wiki.elseta.com/books/wcclite-downloads/page/firmware-and-tools)and run WCC Excel Utility. 2. Select the firmware version from the drop-down menu. 3. Select the Excel file from your computer and click *Convert*. 4. Check if no events in red colour occur. If so, edit the Excel file according to the event text and repeat Step 2. 5. Enter the Host and credentials of WCC Lite, click connect and then *Upload configuration.* [![image-1744036903331.png](https://wiki.elseta.com/uploads/images/gallery/2025-04/scaled-1680-/image-1744036903331.png)](https://wiki.elseta.com/uploads/images/gallery/2025-04/image-1744036903331.png) Another method to upload the configuration is via the web interface: 1. Access the WCC Lite interface via your browser. The default IP address is 192.168.1.1. Enter credentials: [![image-1733135286847.png](https://wiki.elseta.com/uploads/images/gallery/2024-12/scaled-1680-/image-1733135286847.png)](https://wiki.elseta.com/uploads/images/gallery/2024-12/image-1733135286847.png) 2. Upload the Excel configuration: [![image-1733135363443.png](https://wiki.elseta.com/uploads/images/gallery/2024-12/scaled-1680-/image-1733135363443.png)](https://wiki.elseta.com/uploads/images/gallery/2024-12/image-1733135363443.png) 3. After a successful upload, the configuration will appear under the **DOWNLOAD CONFIGURATION** tab: [![image-1733135451404.png](https://wiki.elseta.com/uploads/images/gallery/2024-12/scaled-1680-/image-1733135451404.png)](https://wiki.elseta.com/uploads/images/gallery/2024-12/image-1733135451404.png) 4. If any errors occur during the upload, follow the error messages and fix them according to Excel utility guidelines. ## Files
1. WCC Excel Utility [Download](https://wiki.elseta.com/attachments/660) 2. Example configuration file [Download](https://wiki.elseta.com/attachments/661) 3. ABB meter manual [Download](https://wiki.elseta.com/attachments/662)