# DLMS Serial to IEC61850-server protocol conversion (Wcc Lite FW: 1.7.0) ## Description
**name** | **description** | **device\_alias** | **protocol** | **serial\_number** | **device** | **databits** | **stopbits** | **baudrate** | **parity** |
DLMS Serial | DLMS Serial | DLMS\_Meter | DLMS | 2250259 | PORT1 | 8 | 1 | 4800 | none |
**flowcontrol** | **enable** | **auth** | **logical\_address** | **address\_size** | **client\_address** | **type** | **mode** |
none | 1 | LOW | 1 | 2 | 32 | SN | DLMS-HDLC |
**name** | **description** | **device\_alias** | **protocol** | **bind\_address** |
IEC 61850 Server | IEC 61850 Server | iec\_61850\_server | iec 61850 server | 0.0.0.0 |
**ied\_name** | **access\_point** | **port** | **auth** | **host** | **model\_filename** |
WCCLITE | LD0 | 102 | NONE | 192.168.1.2 | WCC |
**signal\_name** | **device\_alias** | **signal\_alias** | **obis\_job** |
Voltage L1-N | DLMS\_Meter | Voltage\_L1-N | 1.0.32.7.0.255 |
Voltage L2-N | DLMS\_Meter | Voltage\_L2-N | 1.0.52.7.0.255 |
Voltage L3-N | DLMS\_Meter | Voltage\_L3-N | 1.0.72.7.0.255 |
Frequency | DLMS\_Meter | Frequency | 1.0.14.7.0.255 |
Current L3 | DLMS\_Meter | Current\_L3 | 1.0.71.7.0.255 |
**obis\_job** - Objects are identified with the help of OBIS (Object Identification System) codes.
1. The first number of OBIS code defines the media (energy type) to which the metering is related. Nonmedia related information is handled as abstract data. For example all obis\_jobs in the table above starts with numbers 1 which stands for "Electricity related objects". 2. The second number defines the channel number, i.e. the number of the input of a metering equipment having several inputs for the measurement of energy of the same or different types (e.g. in data concentrators, registration units). Data from different sources can thus be identified. The definitions for this value group are independent from the value of the first number. In all obis\_jobs from the table above second number is set to zero which means that no channel is specified. 3. The third number defines the abstract or physical data items related to the information source concerned, for example current, voltage, power, volume, temperature. The definitions depend on the value of the first number. For example in obis\_jobs from the table above number 72 means voltage L3 and number 14 means frequency. 4. The forth number defines types, or the result of the processing of physical quantities identified with the numbers 1 and 3, according to various specific algorithms. The algorithms can deliver energy and demand quantities as well as other physical quantities. In all obis\_jobs from the table above forth number is set to 7 which stands for "Instantaneous value". 5. The value of the fifth number defines further processing or classification of quantities identified by numbers 1 to 4. In case of the first obis\_job number 0 means that all harmonics of the signal along with its fundamental frequency are going to be taken into consideration. 6. The value of the sixth number defines the storage of data, identified by numbers 1 to 5, according to different billing periods. Where this is not relevant, this value group can be used for further classification. In all obis\_jobs from the table above last number is set to 255 which means that data is not used. #### Add signals information for **IEC 61850 server** (Excel **SignalsIEC61850** sheet):**signal\_name** | **device\_alias** | **signal\_alias** | **source\_device\_alias** | **source\_signal\_alias** |
LD0\_\_GGIO\_5\_AnIn1\_mag.f | iec\_61850\_server | LD0\_\_GGIO\_5\_AnIn1\_mag.f | DLMS\_Meter | Voltage\_L1-N |
LD0\_\_GGIO\_5\_AnIn2\_mag.f | iec\_61850\_server | LD0\_\_GGIO\_5\_AnIn2\_mag.f | DLMS\_Meter | Voltage\_L2-N |
LD0\_\_GGIO\_5\_AnIn3\_mag.f | iec\_61850\_server | LD0\_\_GGIO\_5\_AnIn3\_mag.f | DLMS\_Meter | Voltage\_L3-N |
LD0\_\_GGIO\_5\_AnIn4\_mag.f | iec\_61850\_server | LD0\_\_GGIO\_5\_AnIn4\_mag.f | DLMS\_Meter | Frequency |
LD0\_\_GGIO\_5\_AnIn5\_mag.f | iec\_61850\_server | LD0\_\_GGIO\_5\_AnIn5\_mag.f | DLMS\_Meter | Current\_L3 |
**ld\_instance** | **ln\_class** | **ln\_instance** | **cdc** | **data\_object** | **da\_fc** | **number\_type** | **da\_value** | **Log** |
LD0 | GGIO | 5 | MV | AnIn1 | MX | FLOAT32 | mag.f | 1 |
LD0 | GGIO | 5 | MV | AnIn2 | MX | FLOAT32 | mag.f | 1 |
LD0 | GGIO | 5 | MV | AnIn3 | MX | FLOAT32 | mag.f | 1 |
LD0 | GGIO | 5 | MV | AnIn4 | MX | FLOAT32 | mag.f | 1 |
LD0 | GGIO | 5 | MV | AnIn5 | MX | FLOAT32 | mag.f | 1 |