Testing IOMod 8DI8DO IEC-103

Initial Setup

The first thing to do when setting up is to connect the IOMod to the computer using The Vinci Expert to convert from RS485 to USB. You need to connect it like in the diagram depicted below.



To test IOmod with default settings, the user connects the device through RS485 to IEC 60870-5-103 master. For example, using “The Vinci Expert” as a serial interface converter and adapter to PC with “The Vinci” software. When opening “The Vinci” software, choose IEC 60870-5-103 – Master mode. Initial settings – 9600 baud rate; 8 data, no parity, 1 stop bit. Press Start, send Time synchronization, General interrogation, and go to the “Statistic” tab:


image-1641224072271.png

Fig. 1. Testing IOMOD device with “THE VINCI” software

As seen in Figure 1, Outputs and inputs are shown with info numbers 1-8, and function types are 128 and 160 respectively.

General Interrogation, Time Synchronization, and General Command options can be found on the right side of the program, in the “System” tab.

Output commands are controlled by the “General command” window on the right side of the program, in the “System” tab, with Output address (Function type) 128, and output number (Info number).

Figure 2 shows the 6th output command sent and the “CMD ACK”  response received.

image-1641224017139.png

Fig. 2 Replies from IOmod device after a command has been sent through “THE VINCI” software