# CLMod manual # CLMod manual ##### **Introduction** CL MOD is RS485 interface converter-splitter to 6X 20mA current loop interface designed to be used with power meters (SLAVE device with current loop interface) and data loggers, gateways or other equipment (MASTER device with half-duplex RS485 interface). This converter was developed to read multiple meters data over 20mA current loop interface with long distance lines up to 2km. CLMod with 6 current loop interfaces is capable to readout data up to 30 meters (5 meters per single current loop). CLMod is protocol agnostic and can be used with any type of protocol. ##### **Features** ⦁ 6X 3kVRMS isolated 20mA current loop interface; ⦁ supports up to 5 power meters on each current loop (30 meters total); ⦁ baud rates: 1200 to 9600; ⦁ 24VDC (21.6-26.4VDC full range) power supply; ⦁ automatic open loop detection and disconnection; ⦁ fail indication for each current loop; ⦁ integrated current loop protection (optional); ⦁ operating range from -40°C to +80°C; ⦁ dimensions 101x119x17.5mm. ⦁ LED indication of data transmission on every current loop interface ⦁ Compatible with Elgama Elektronika meters ⦁ RS485 interface for RTU/Datalogger ##### **Device operational information** CL MOD connects to a MASTER device over RS485 half-duplex interface, splits and transmits MASTER requests into 6 current loop interfaces. Power meters connects to current loop interface in series (up to 5 meters on each CL interface). One power meter (SLAVE device) can transmit simultaneously, so some time delay need to be added between MASTER’s requests according to selected baud rate. CL MOD automatically detects and disconnects open current loop (not connected or flooding) and has a status indication for each of 6 current loop interfaces. CL MOD automatically reconnects to current loop when fault is fixed. Indication examples are demonstrated on Fig 1. [](https://wiki.elseta.com/uploads/images/gallery/2022-11/image-1667895586578.png) Fig 1. CL MOD indication examples ##### **Technical information**
**System** | ||
1\. | Dimension | 101 x 119 x 17.5 mm |
2. | Case | ABS, black |
3. | Working environment | Indoors |
4. | Working temperature | -40 ÷ +80°C |
5. | Recommended operating conditions | 5 – 60°C and 20 – 80% RH; |
**Electrical specifications** | ||
6. | Power Supply | 24VDC, 4W (nominal); 21.6-26.4VDC (full range) |
7. | Current loop voltage | 24VDC (max) |
8. | Current loop IMARK | ≥12mA |
9. | Current loop ISPACE | ≤3mA |
10. | CL1-CL6 surge protection (optional) | 20kA, 8/20µs |